Inspection Status: Passed
Inspection History: COT - LCME - Mechanical Intermediate
| Date |
Description |
Inspector |
Results |
Comments |
| 09/14/2021 |
COT - LCME - Mechanical Intermediate |
DMUNIZ |
Approved |
Entered by RSALDAT1 - Approved. |
| 05/14/2021 |
COT - LCME - Mechanical Intermediate |
DMUNIZ |
Partial Approval |
Entered by VLEON1 - Partial, Hydrostatic test on chilled lines complete.
|
| 04/22/2021 |
COT - LCME - Mechanical Intermediate |
DMUNIZ |
Partial Approval |
Entered by VLEON1 - PARTIAL, Hydroponic piping installed and tested at following units ( CRAH-3B, CRAH-1A, CRAH-1B, FCU-1A, FCU-1B, AHU-1A, AHU-1B)
|
| 04/21/2021 |
COT - LCME - Mechanical Intermediate |
DMUNIZ |
Partial Approval |
Entered by VLEON1 - Partial, 1st and 2nd floor Low/Medium pressure ducts installed and ok to start insulation. OB |
| 03/19/2021 |
COT - LCME - Mechanical Intermediate |
DMUNIZ |
Partial Approval |
Entered by VLEON1 - PARTIAL, Chilled main lines installed and under air test for 1st floor & ok to insulate lines. IDF 221 chilled lines installed below 2nd floor. AHU’s installed GL 12-17 below second floor. |