Inspection Status: Canceled
Inspection History: COT - RSEL - Electrical Final
| Date |
Description |
Inspector |
Results |
Comments |
| 11/07/2022 |
COT - RSEL - Electrical Final |
|
Canceled |
Inspection Canceled |
| 06/17/2021 |
COT - RSEL - Electrical Final |
RELEFANTE |
Denied |
Entered by VLEON1 - DE( wrong size wire for solar system in the main panel and disconnect. Did not have the proper size on the wire from brown rod to main electrical panel. Did not have all required labels at this time.) |
| 09/03/2020 |
COT - RSEL - Electrical Final |
WGALLAGHER |
Not ready for Inspection |
Entered by JSCHNEI2 - Not ready please insure accurate plans are available and tech needs a ladder to access arrays |
| 08/12/2020 |
COT - RSEL - Electrical Final |
DMUNIZ |
Not ready for Inspection |
Entered by JSCHNEI2 - Not Ready |