Inspection History Details
Inspection Status: Passed
Inspection History: COT - FCON - Fire - Final
Permit Number - T20CM03665
Inspection Description - COT - FCON - Fire - Final
Inspection Status - Passed
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/08/2020 | COT - FCON - Fire - Final | jvincent | Approved | Entered by JVINCEN1 - Approved per Cbasaldua |
12/02/2020 | COT - FCON - Fire - Final | CBASALDUA | Denied | Entered by CBASALD1 - 1. Add FDC sign 2. Add Riser Room/FACP room sign to wall next to stairs 3. Remove slide bolt from rear exit door and change hardware 4. Need 15in address numbers on exterior of building 5. Add suite numbers to front of store and rear door |