Permit: T20CM03312

Parcel: 12402023B


Addresses:

1712 E SPEEDWAY BL

Inspection Status: Approved

Inspection History: ELECTRIC - CONSTRUCTION POWER

Date Description Inspector Results Comments
07/09/2020 ELECTRIC - CONSTRUCTION POWER Approved Approved Clearance, Code: RECN. Fire damage, no service upgrade..
07/02/2020 ELECTRIC - CONSTRUCTION POWER Denied All 11 are denied. All MC cable needs to be attached or clamped 12 inches from all boxes and fixtures. Pex piping must be 12 inches away from all recessed lighting. DWV pipe is not under test. STOPPED INSPECTION