Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
Permit Number - T20CM02759
Inspection Description - MECHANICAL - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/18/2022 | MECHANICAL - INTERMEDIATE | Approved | Approved | |
01/10/2022 | MECHANICAL - INTERMEDIATE | Denied | de One mini is overfused, in wrong location for disconnect access, and needs securing of Hvac lines to the building along with physical damage and UV damage protection. The 2nd mini needs to be completely re-installed on the exterior components, with appropriate location, etc., etc. 3rd - is the wall a/c utilizing the appropriate sized circuit, with access to dedicated outlet? |