Permit: T20CM02633

Parcel: 133381990

Inspection Status: Passed

Inspection History: COT - LCBU - Framing

Permit Number - T20CM02633

Inspection Description - COT - LCBU - Framing

Inspection Status - Passed

Date Description Inspector Results Comments
04/18/2022 COT - LCBU - Framing KEN Approved Entered by KKARSEN1 - TRUSS PLANS FILED
04/13/2022 COT - LCBU - Framing WGALLAGHER Partial Approval Entered by NGARCIA3 - PARTIAL APPROVAL NEED APPROVED TRUSS CALCS