Permit: T20CM02339

Parcel: 123152900


Addresses:

1131 E LEE ST

Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Date Description Inspector Results Comments
07/08/2020 PLUMBING - ROUGH, SOIL Approved . Approved
07/06/2020 PLUMBING - ROUGH, SOIL Denied denied
1- I left a message at (520) 891-9067 at 8:18 am to call me so that we can set up a video inspection time today.
07/06/2020 PLUMBING - ROUGH, SOIL Denied denied 1- Shall provide a directional fitting at the point of connection to the existing bldg. drain. 2- Shall provide a 3 x 2 left side inlet at water closet and shower connection. 3- Shall provide Mission Specialty couplings when transitioning from ABS to Cast iron. 4- Re test the DWV system.