Inspection Status: Not Ready
Inspection History: COT - RSPL - Plumbing Final
| Date |
Description |
Inspector |
Results |
Comments |
| 10/27/2022 |
COT - RSPL - Plumbing Final |
|
Not Ready |
|
| 02/24/2023 |
COT - RSPL - Plumbing Final |
|
Not Ready |
Secure whips on a/c. change out fuses, add cover plate. Lighting above tub needs to be at 8’. Receptacle in laundry room needs to be gfci. A pan is required underneath water heater. Flute vent in laundry room is backwards. Missing hammer arrestor for dishwasher, fridge and laundry room. Clean out needs to be cut to grade level. add elbows to exterior pipes. |
| 03/10/2023 |
COT - RSPL - Plumbing Final |
|
Passed |
Water hammer arresters were installed on dishwasher, ice maker, and laundry faucets. Sewer clean out cap was cut down level with ground. |