Permit: T20CM01567

Parcel: 120084400


Addresses:

216 W OKLAHOMA ST

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
07/08/2020 PLUMBING - FINAL Approved approved
06/19/2020 PLUMBING - FINAL Denied denied
1- Shall provide the required test gage of 15 lbs max with 1/10th in tenth increments and system test of 10 psi minimum.
2- Shall provide combustion air openings for water heater room.
3- Shall provide (3) sheet metal screws per joint on the water heater draft collar and all vent connector joints.
4- Shall terminate the water heater t & p drain to daylight or provide a drain pan and cap off pan drain outlet and terminate the t & p drain into the pan.
5- Shall provide a sediment trap for the water heater and AC unit.
6- Shall seal the gas line penetration at exterior wall.
7- Shall provide a ground bond on gas line.
8- Shall provide a carbon monoxide detector and locate it in the hallway to the bedrooms.
05/20/2020 PLUMBING - FINAL Denied denied
1- Pressure test gage was at zero psi. Shall provide a minimum of 10 psi for 15 minutes on the entire gas system. Check the system for leaks.
05/12/2020 PLUMBING - FINAL Denied 1- I left a message at 8:56am for someone to call me so that we could set up a video inspection time for today before 3:00 pm.
05/08/2020 PLUMBING - FINAL Denied 1- I left a message at 8:53 am on (520) 551-7790 for some to contact before 3:00 pm to schedule a video inspection time for today.