Permit: T20CM01382

Parcel: 126122550


Addresses:

4620 E 10TH ST

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
03/09/2020 MECHANICAL - FINAL Approved
03/05/2020 MECHANICAL - FINAL Partial Approval Breaker changed, but condensation is still less than 6” above grade.
03/04/2020 MECHANICAL - FINAL Denied Max ampicity for unit is 50 amps, 60 amp breaker installed.
Condensate is against foundation, needs to be 6 inches away and 6 inches above ground minimum