Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/28/2020 | ELECTRIC - SERVICE UPGRADE | Approved | ||
| 02/25/2020 | ELECTRIC - SERVICE UPGRADE | Denied | 1- Shall land the gas bond to the supply side o& the gas meter not the service side of meter. | |
| 02/24/2020 | ELECTRIC - SERVICE UPGRADE | Denied | 1- Shall provide two ground rod electrode conductors an bond the gas line. 2- Shall secure the Ufer ground conductor to the wall. |