Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T20CM00914

Parcel: 119044980


Addresses:

135 W VETERANS BL

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
02/28/2020 ELECTRIC - SERVICE UPGRADE Approved
02/25/2020 ELECTRIC - SERVICE UPGRADE Denied 1- Shall land the gas bond to the supply side o& the gas meter not the service side of meter.
02/24/2020 ELECTRIC - SERVICE UPGRADE Denied 1- Shall provide two ground rod electrode conductors an bond the gas line.
2- Shall secure the Ufer ground conductor to the wall.