Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - UNDERGROUND
Permit Number - T20CM00826
Inspection Description - ELECTRIC - UNDERGROUND
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/13/2020 | ELECTRIC - UNDERGROUND | Approved | Approved | |
09/01/2020 | ELECTRIC - UNDERGROUND | Partial Approval | Partial. Upper Plaza, 5 each light pole caissons and cages. User and conduits are in place. Ok to place concrete in progress areas. | |
08/27/2020 | ELECTRIC - UNDERGROUND | Partial Approval | Partial. North light pole caisson footings; cages in place. Ok to place concrete in progress areas. | |
08/05/2020 | ELECTRIC - UNDERGROUND | Partial Approval | Partial. Conduits (6 @ 3" and 1 @ 4") from building to transformer area. Ok to cover progress area. | |
06/02/2020 | ELECTRIC - UNDERGROUND | Partial Approval | Partial. Conduits, (1”-3”) central and northeast portion of site. Ok to cover progress areas. | |
05/28/2020 | ELECTRIC - UNDERGROUND | Not ready for Inspection | Not ready. Contractor canceled. | |
05/27/2020 | ELECTRIC - UNDERGROUND | Partial Approval | Partial. Conduits (2 1/2”-4”) at Room #102 to Elevator mechanical room. Ok to cover progress area. |