Permit: T20CM00750

Parcel: 134240760


Addresses:

6330 E ELI DR

Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Date Description Inspector Results Comments
04/20/2020 MECHANICAL - INTERMEDIATE Approved
02/25/2020 MECHANICAL - INTERMEDIATE Denied Condensate piping not properly supported, provide maximum 48 inch spacing, provide pressure-treated lumber or equal. Condensate piping to be coated for UV protection. Condensate piping not properly terminated. Unit data plate not properly identified. Electrical conduit requires roof jack at all roof penetrations. Service receptacle not properly wired, provide circuit from maximum 20 amp breaker, outlet is to be GFCI protected.
02/21/2020 MECHANICAL - INTERMEDIATE Not ready for Inspection Provide access to roof.
02/19/2020 MECHANICAL - INTERMEDIATE Denied no access and no ladder called contact and left message no answer