Permit: T20CM00481

Parcel: 137051000


Addresses:

5065 S 12TH AV

Inspection Status: Approved

Inspection History: SITE - SEWER

Date Description Inspector Results Comments
09/30/2021 SITE - SEWER Approved Approved
07/21/2020 SITE - SEWER Denied denied
1- Shall provide directional fittings for all horizontal to horizontal drainage.
2- Shall provide a double pattern wye when connecting to branch lines together.
3- No threaded fittings allowed in concealed locations.
4- Shall provide long sweeps for all vertical to horizontal drainage.
5- Shall provide vents for all floor drains and floor sinks.
6- Shall locate the outlet of the vents to water closets above the center line of soil line.
7- Shall provide a 10 foot water test on the system.denied