Inspection Status: Passed
Inspection History: COT - RSEL - Service Upgrade
| Date |
Description |
Inspector |
Results |
Comments |
| 02/20/2020 |
COT - RSEL - Service Upgrade |
WGALLAG1 |
Approved |
Entered by DMERANZ1 - OK FOR INCR |
| 02/03/2020 |
COT - RSEL - Service Upgrade |
MRAMBER |
Denied |
Entered by SFLORES2 - Neutral wire not properly identified. Neutral wire not landed out proper terminal. White wire not to be used as a hot leg. Provide approved hub connectors at top of panel |
| 01/22/2020 |
COT - RSEL - Service Upgrade |
RCHANDLER |
Correction Required |
Entered by DMERANZ1 - 1-Expose grounding electrode conductor and the connection of it to both ground rods.
2--Bond water piping.
3-Bond gas piping. Note: Service is energized and meter section is unsealed. |