Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/30/2020 | FIRE - FINAL | Approved | ||
| 11/20/2020 | FIRE - FINAL | Partial Approval | Pending payment of sprinkler permit Verify places of assembly permit Approved to obtain Temporary Certificate of Occupancy |
|
| 11/18/2020 | FIRE - FINAL | Partial Approval | -Complete kitchen hood inspection for Ansul system -Exit from the rear of the kitchen must extend all the way to the public way. Install panic hardware on gate in storage area behind kitchen -Post max occupancy load sign 164 people in lobby -Places of assembly require an operational permit through the Tucson Fire Department. (Application left with party on site) -Install missing electrical outlet covers in east storage room next to riser room -Mount fire extinguishers in dining area and kitchen |