Permit: T20CM00313

Parcel: 12513068A

Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Permit Number - T20CM00313

Inspection Description - MECHANICAL - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
11/01/2021 MECHANICAL - INTERMEDIATE Approved 1010, 3057,2005,3005,1015,3040, 1030, 1045, 2061, 1025, 3036, 4036, 3050, 1005, 2010, 1036, 2036, 2090, 3090, 4090, 2085, 2099. Approved.
09/28/2021 MECHANICAL - INTERMEDIATE Cancelled IVRS - AP canceled
09/27/2021 MECHANICAL - INTERMEDIATE Cancelled IVRS - AP canceled
09/15/2021 MECHANICAL - INTERMEDIATE Cancelled IVRS - AP canceled
09/14/2021 MECHANICAL - INTERMEDIATE Partial Approval 1035, 2035, 3035, 4035, 1044. Partial. Room 3211.
09/03/2021 MECHANICAL - INTERMEDIATE Cancelled Canceled by contractor
09/02/2021 MECHANICAL - INTERMEDIATE Cancelled IVRS - AP canceled
09/01/2021 MECHANICAL - INTERMEDIATE Not ready for Inspection Not ready
08/31/2021 MECHANICAL - INTERMEDIATE Not ready for Inspection Not ready
08/31/2021 MECHANICAL - INTERMEDIATE Cancelled IVRS - AP canceled
08/30/2021 MECHANICAL - INTERMEDIATE Cancelled IVRS - AP canceled
08/30/2021 MECHANICAL - INTERMEDIATE Not ready for Inspection Not ready
08/27/2021 MECHANICAL - INTERMEDIATE Not ready for Inspection Not ready. Contractor cancelled
08/27/2021 MECHANICAL - INTERMEDIATE Cancelled IVRS - AP canceled
08/26/2021 MECHANICAL - INTERMEDIATE Cancelled IVRS - AP canceled
08/26/2021 MECHANICAL - INTERMEDIATE Partial Approval Partial. Building #4; Units 3201 - 3204. 0k to insulate and cover walls.
08/25/2021 MECHANICAL - INTERMEDIATE Cancelled IVRS - AP canceled
08/20/2021 MECHANICAL - INTERMEDIATE Partial Approval Partial. Interior duct systems for apartments 3205-3210. Ok to cover walls.
08/19/2021 MECHANICAL - INTERMEDIATE Cancelled IVRS - AP canceled
08/18/2021 MECHANICAL - INTERMEDIATE Not ready for Inspection Not ready. Contractor cancelled.
08/17/2021 MECHANICAL - INTERMEDIATE Cancelled IVRS - AP canceled
08/17/2021 MECHANICAL - INTERMEDIATE Not ready for Inspection Not ready
08/16/2021 MECHANICAL - INTERMEDIATE Cancelled IVRS - AP canceled
08/12/2021 MECHANICAL - INTERMEDIATE Partial Approval 1035, 2035, 3035, 4035. 1044. Partial. Units 3401 and 3402.
08/12/2021 MECHANICAL - INTERMEDIATE Cancelled IVRS - AP canceled
08/11/2021 MECHANICAL - INTERMEDIATE Partial Approval Dolphins section level 4. Units and 3402 and in Vikings section 3425. Level 4 storage rooms 409 A thru E.
08/11/2021 MECHANICAL - INTERMEDIATE Cancelled IVRS - AP canceled
08/09/2021 MECHANICAL - INTERMEDIATE Not ready for Inspection not ready
08/09/2021 MECHANICAL - INTERMEDIATE Cancelled IVRS - AP canceled
08/06/2021 MECHANICAL - INTERMEDIATE Cancelled IVRS - AP canceled
08/06/2021 MECHANICAL - INTERMEDIATE Cancelled Canceled by contractor
08/05/2021 MECHANICAL - INTERMEDIATE Partial Approval Partial. Level 4. Stealers section. Units 3405 thru 3408.
08/05/2021 MECHANICAL - INTERMEDIATE Cancelled IVRS - AP canceled
08/04/2021 MECHANICAL - INTERMEDIATE Cancelled IVRS - AP canceled
08/03/2021 MECHANICAL - INTERMEDIATE Partial Approval 1044, 1025, 2035, 3035, 4035. Partial. Level 3. Units 3311 to 3317.
08/03/2021 MECHANICAL - INTERMEDIATE Cancelled IVRS - AP canceled
08/02/2021 MECHANICAL - INTERMEDIATE Cancelled IVRS - AP canceled
07/30/2021 MECHANICAL - INTERMEDIATE Partial Approval Partial. Building #3, Level #3: Room Units 3411, 3412, 3413..
07/29/2021 MECHANICAL - INTERMEDIATE Not ready for Inspection Not ready. Contractor cancelled.
07/29/2021 MECHANICAL - INTERMEDIATE Not ready for Inspection Not ready. Contractor cancelled.
07/29/2021 MECHANICAL - INTERMEDIATE Cancelled IVRS - AP canceled
07/28/2021 MECHANICAL - INTERMEDIATE Cancelled IVRS - AP canceled
07/28/2021 MECHANICAL - INTERMEDIATE Partial Approval Partial. Level four. Steeler section. Units 3414, 3415, 3416.
07/28/2021 MECHANICAL - INTERMEDIATE Partial Approval Partial. Level two. Dolphin section. Corridors and room number 208
07/27/2021 MECHANICAL - INTERMEDIATE Not ready for Inspection 1035, 2035, 3035, 4035. Not ready. Data communication lines not installed. Installer is placing data boxes back to back in fire walls.
07/27/2021 MECHANICAL - INTERMEDIATE Cancelled IVRS - AP canceled
07/26/2021 MECHANICAL - INTERMEDIATE Cancelled
07/26/2021 MECHANICAL - INTERMEDIATE Cancelled IVRS - AP canceled
07/23/2021 MECHANICAL - INTERMEDIATE Cancelled IVRS - AP canceled
07/23/2021 MECHANICAL - INTERMEDIATE Cancelled CANCELLED BY CONTRACTOR
07/22/2021 MECHANICAL - INTERMEDIATE Cancelled IVRS - AP canceled
07/22/2021 MECHANICAL - INTERMEDIATE Cancelled CANCELLED BY CONTRACTOR
07/21/2021 MECHANICAL - INTERMEDIATE Cancelled IVRS - AP canceled
07/16/2021 MECHANICAL - INTERMEDIATE Partial Approval Partial. Level #3; Room Units 2321 - 2332.
07/15/2021 MECHANICAL - INTERMEDIATE Partial Approval 1044, 1035, 2035, 3035, 4035. Partial. Level two. Dolphin section. Units 3219 and 3220. Level four. Viking section. Unit 3417 through 3421.
07/15/2021 MECHANICAL - INTERMEDIATE Cancelled IVRS - AP canceled
07/14/2021 MECHANICAL - INTERMEDIATE Partial Approval 1044. 1035, 2035,3035, 4035. Partial. Level 4. Vikings section. Units 3424, 3423, 3422.
07/13/2021 MECHANICAL - INTERMEDIATE Cancelled IVRS - AP canceled
07/12/2021 MECHANICAL - INTERMEDIATE Not ready for Inspection 1044, 1035, 2035, 4035, 3035. Partial. Level four. Vikings section. Not ready
07/09/2021 MECHANICAL - INTERMEDIATE Cancelled IVRS - AP canceled
07/08/2021 MECHANICAL - INTERMEDIATE Cancelled Canceled by contractor
07/08/2021 MECHANICAL - INTERMEDIATE Cancelled IVRS - AP canceled
07/07/2021 MECHANICAL - INTERMEDIATE Cancelled IVRS - AP canceled
07/07/2021 MECHANICAL - INTERMEDIATE Cancelled Canceled by contractor
07/06/2021 MECHANICAL - INTERMEDIATE Cancelled Canceled by contractor
07/06/2021 MECHANICAL - INTERMEDIATE Cancelled IVRS - AP canceled
07/01/2021 MECHANICAL - INTERMEDIATE Cancelled IVRS - AP canceled
07/01/2021 MECHANICAL - INTERMEDIATE Cancelled IVRS - AP canceled
06/30/2021 MECHANICAL - INTERMEDIATE Not ready for Inspection
06/30/2021 MECHANICAL - INTERMEDIATE Cancelled IVRS - AP canceled
06/29/2021 MECHANICAL - INTERMEDIATE Cancelled IVRS - AP canceled
06/28/2021 MECHANICAL - INTERMEDIATE Not ready for Inspection
06/28/2021 MECHANICAL - INTERMEDIATE Cancelled IVRS - AP canceled
06/25/2021 MECHANICAL - INTERMEDIATE Cancelled IVRS - AP canceled
06/25/2021 MECHANICAL - INTERMEDIATE Cancelled CANCELLED BY CONTRACTOR
06/24/2021 MECHANICAL - INTERMEDIATE Cancelled IVRS - AP canceled
06/24/2021 MECHANICAL - INTERMEDIATE Partial Approval Partial. Level three. Steelers section. Units 3318 thru 3323 and corridor
06/23/2021 MECHANICAL - INTERMEDIATE Cancelled CANCELLED BY CONTRACTOR
06/23/2021 MECHANICAL - INTERMEDIATE Cancelled IVRS - AP canceled
06/22/2021 MECHANICAL - INTERMEDIATE Cancelled CANCELLED BY CONTRACTOR
06/22/2021 MECHANICAL - INTERMEDIATE Cancelled IVRS - AP canceled
06/21/2021 MECHANICAL - INTERMEDIATE Cancelled IVRS - AP canceled
06/15/2021 MECHANICAL - INTERMEDIATE Not ready for Inspection NOT READY CONTRACTOR CANCELLED
06/14/2021 MECHANICAL - INTERMEDIATE Cancelled IVRS - AP canceled
06/14/2021 MECHANICAL - INTERMEDIATE Partial Approval Partial. Steelers section. Level two. Units 3221 through 3226 and Corridor ceiling.
06/10/2021 MECHANICAL - INTERMEDIATE Cancelled IVRS - AP canceled
06/03/2021 MECHANICAL - INTERMEDIATE Cancelled IVRS - AP canceled
06/02/2021 MECHANICAL - INTERMEDIATE Partial Approval Partial. Units 3101 thru. 3103. Level 1 Steelers section. Corridor
06/02/2021 MECHANICAL - INTERMEDIATE Cancelled IVRS - AP canceled
06/01/2021 MECHANICAL - INTERMEDIATE Cancelled IVRS - AP canceled
05/28/2021 MECHANICAL - INTERMEDIATE Partial Approval Partial. Viking section. Level two. Corredor section.
05/28/2021 MECHANICAL - INTERMEDIATE Partial Approval Partial. Level three storage area rooms, 312B, 312C, 312D.
05/27/2021 MECHANICAL - INTERMEDIATE Cancelled IVRS - AP canceled
05/27/2021 MECHANICAL - INTERMEDIATE Cancelled CANCELLED BY CONTRACTOR
05/27/2021 MECHANICAL - INTERMEDIATE Cancelled IVRS - AP canceled
05/26/2021 MECHANICAL - INTERMEDIATE Cancelled IVRS - AP canceled
05/25/2021 MECHANICAL - INTERMEDIATE Not ready for Inspection NOT READY CONTRACTOR CANCELLED
05/24/2021 MECHANICAL - INTERMEDIATE Not ready for Inspection
05/24/2021 MECHANICAL - INTERMEDIATE Cancelled IVRS - AP canceled
05/21/2021 MECHANICAL - INTERMEDIATE Cancelled IVRS - AP canceled
05/20/2021 MECHANICAL - INTERMEDIATE Cancelled IVRS - AP canceled
05/20/2021 MECHANICAL - INTERMEDIATE Cancelled CANCELLED BY CONTRACTOR
05/19/2021 MECHANICAL - INTERMEDIATE Not ready for Inspection NOT READY CANCELLED BY CONTRACTOR
05/19/2021 MECHANICAL - INTERMEDIATE Cancelled IVRS - AP canceled
05/18/2021 MECHANICAL - INTERMEDIATE Cancelled CANCELLED BY CONTRACTOR
05/18/2021 MECHANICAL - INTERMEDIATE Cancelled IVRS - AP canceled
05/17/2021 MECHANICAL - INTERMEDIATE Cancelled CANCELLED BY CONTRACTOR
05/17/2021 MECHANICAL - INTERMEDIATE Cancelled IVRS - AP canceled
05/14/2021 MECHANICAL - INTERMEDIATE Cancelled IVRS - AP canceled
05/13/2021 MECHANICAL - INTERMEDIATE Partial Approval PARTIAL UNITS 3324 THROUGH 3330
05/13/2021 MECHANICAL - INTERMEDIATE Cancelled IVRS - AP canceled
05/12/2021 MECHANICAL - INTERMEDIATE Cancelled CANCELLED BY CONTRACTOR
05/12/2021 MECHANICAL - INTERMEDIATE Cancelled IVRS - AP canceled
05/11/2021 MECHANICAL - INTERMEDIATE Cancelled IVRS - AP canceled
05/10/2021 MECHANICAL - INTERMEDIATE Cancelled IVRS - AP canceled
05/07/2021 MECHANICAL - INTERMEDIATE Cancelled IVRS - AP canceled
05/06/2021 MECHANICAL - INTERMEDIATE Partial Approval Partial. Vikings section. Level 1 corridors. Trash chute room 121 and custodial room 122.
05/06/2021 MECHANICAL - INTERMEDIATE Cancelled IVRS - AP canceled
05/05/2021 MECHANICAL - INTERMEDIATE Cancelled IVRS - AP canceled
05/05/2021 MECHANICAL - INTERMEDIATE Cancelled CANCELLED BY CONTRACTOR
05/04/2021 MECHANICAL - INTERMEDIATE Cancelled IVRS - AP canceled
05/03/2021 MECHANICAL - INTERMEDIATE Cancelled CANCELLED BY CONTRACTOR
04/30/2021 MECHANICAL - INTERMEDIATE Cancelled IVRS - AP canceled
04/30/2021 MECHANICAL - INTERMEDIATE Partial Approval PARTIAL FOR UNITS 3227 THRU 3233
04/29/2021 MECHANICAL - INTERMEDIATE Cancelled CANCELLED BY CONTRACTOR
04/29/2021 MECHANICAL - INTERMEDIATE Cancelled IVRS - AP canceled
04/28/2021 MECHANICAL - INTERMEDIATE Cancelled IVRS - AP canceled
04/27/2021 MECHANICAL - INTERMEDIATE Cancelled IVRS - AP canceled
04/26/2021 MECHANICAL - INTERMEDIATE Cancelled IVRS - AP canceled
04/23/2021 MECHANICAL - INTERMEDIATE Cancelled IVRS - AP canceled
04/22/2021 MECHANICAL - INTERMEDIATE Partial Approval Partial. Level one. Vikings section. Units 3104 and 3105. Garage units 116, 117, 118.
04/21/2021 MECHANICAL - INTERMEDIATE Cancelled IVRS - AP canceled
04/19/2021 MECHANICAL - INTERMEDIATE Not ready for Inspection
04/16/2021 MECHANICAL - INTERMEDIATE Cancelled IVRS - AP canceled
04/14/2021 MECHANICAL - INTERMEDIATE Not ready for Inspection
04/14/2021 MECHANICAL - INTERMEDIATE Cancelled IVRS - AP canceled
04/13/2021 MECHANICAL - INTERMEDIATE Not ready for Inspection
04/13/2021 MECHANICAL - INTERMEDIATE Cancelled IVRS - AP canceled
04/12/2021 MECHANICAL - INTERMEDIATE Cancelled IVRS - AP canceled
04/09/2021 MECHANICAL - INTERMEDIATE Cancelled IVRS - AP canceled
04/09/2021 MECHANICAL - INTERMEDIATE Cancelled Cancel.
04/08/2021 MECHANICAL - INTERMEDIATE Cancelled IVRS - AP canceled
04/07/2021 MECHANICAL - INTERMEDIATE Partial Approval Partial. Level three. Eagles section. Units 3331 thru 3340.
04/07/2021 MECHANICAL - INTERMEDIATE Cancelled IVRS - AP canceled
04/06/2021 MECHANICAL - INTERMEDIATE Cancelled IVRS - AP canceled
04/06/2021 MECHANICAL - INTERMEDIATE Not ready for Inspection
04/05/2021 MECHANICAL - INTERMEDIATE Cancelled IVRS - AP canceled
03/31/2021 MECHANICAL - INTERMEDIATE Cancelled CANCELLED BY CONTRACTOR NOT READY
03/30/2021 MECHANICAL - INTERMEDIATE Cancelled IVRS - AP canceled
03/26/2021 MECHANICAL - INTERMEDIATE Partial Approval Partial. Dolphins section. Make up air duct from roof to second floor, OK to insulate
03/22/2021 MECHANICAL - INTERMEDIATE Approved Level two. Eagle section. Unit 3243 through 3234.
03/08/2021 MECHANICAL - INTERMEDIATE Partial Approval PARTIAL UNITS 3110 THRU 3116
02/22/2021 MECHANICAL - INTERMEDIATE Partial Approval PARTIAL EAGLE SECTION LEVEL 3 UNITS 3331 THRU 3338
02/10/2021 MECHANICAL - INTERMEDIATE Partial Approval PARTIAL UNITS 3234 THRU 3243