Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/08/2019 | FIRE - FINAL | Approved | HOOD FINAL COMPLETE ON 11/07/19 - APPROVED BY INSPECTOR BASALDUA | |
| 10/31/2019 | FIRE - FINAL | Denied | -Kitchen hood suppression system needs to be modified for current appliances and put into service - seperate permit required through the Tucson Fire Department -Remove non required sprinkler system in kitchen -Provide and mount fire extinguishers - 1- 2A 10BC and 1 -K Class in kitchen -Electrical outlet at sink area shall be GFCI protected -Post occupant load sign -Operational permit for places of assembly required through TFD Approved contractors can be found at www.Northwestfire.org |