12/03/2019 FIRE INSP - OPERATIONAL PERMIT Correction Required -company not on approved list of contractors.
-plans need to be minimum 24x36"
-need three sets of plans.
-sequence of operations missing.
-does bldg have FACP?
-central unit located too close to POU.
-battery backup info missing.