Inspection History Details
Inspection Status: Approved
Inspection History: FIRE INSP - OPERATIONAL PERMIT
Permit Number - T19FO00755
Inspection Description - FIRE INSP - OPERATIONAL PERMIT
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/29/2021 | FIRE INSP - OPERATIONAL PERMIT | Approved | ||
12/13/2019 | FIRE INSP - OPERATIONAL PERMIT | Partial Approval | plans approved | |
10/03/2019 | FIRE INSP - OPERATIONAL PERMIT | Denied | Notes from plan review: 1. Did not indicate if fire alarm on site. 2. Could not locate sensor #1. 3. Sequence of operations missing. 4. Central unit too close to POU. |