Inspection History Details
Inspection Status: Approved
Inspection History: FIRE INSP - OPERATIONAL PERMIT
Permit Number - T19FO00534
Inspection Description - FIRE INSP - OPERATIONAL PERMIT
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/16/2020 | FIRE INSP - OPERATIONAL PERMIT | Approved | ||
03/06/2020 | FIRE INSP - OPERATIONAL PERMIT | Partial Approval | Need the following three items prior to full final: -locate, label and lock circuit breaker. -updated zone list to central station. email the paperwork. -add 704 diamond to rear gates. |
|
03/06/2020 | FIRE INSP - OPERATIONAL PERMIT | Partial Approval | Waiting on one item: 1) Updated zone list from central station. Email paperwork. |
|
10/03/2019 | FIRE INSP - OPERATIONAL PERMIT | Denied | 1. Detectors not on plans. 2. Central unit too close to POU. 3. Sequence of operations missing. xb 4. Did not indicate if there's a fire alarm at location. |
|
07/16/2019 | FIRE INSP - OPERATIONAL PERMIT | Denied | 1. Need full size drawings. 2. Need locations of sensors, notification appliances and central unit. 3. Need data sheets on CO2 alarm equipment. |