Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T19FC00839

Parcel: 132130750


Addresses:

3300 S PARK AV


Inspection Status: Passed

Inspection History: COT - FCON - Underground Pressure

Permit Number - T19FC00839

Inspection Description - COT - FCON - Underground Pressure

Inspection Status - Passed

Date Description Inspector Results Comments
11/01/2019 COT - FCON - Underground Pressure gsereno1 Approved Entered by GSERENO1 - Inspection 2. Re-inspection fee added for 3rd UG inspection.
10/31/2019 COT - FCON - Underground Pressure gsereno1 Denied Entered by GSERENO1 - Inspection one. Gauge read 70 psi. Shall be 200 psi for 2 hours.