Permit: T19FC00795

Parcel: 141366820


Addresses:

7401 S WILMOT RD


Inspection Status: Approved

Inspection History: FIRE SPKLR - FINAL

Permit Number - T19FC00795

Inspection Description - FIRE SPKLR - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
05/20/2020 FIRE SPKLR - FINAL Approved
05/15/2020 FIRE SPKLR - FINAL Not ready for Inspection see notes for partial
need locking FDC caps
04/22/2020 FIRE SPKLR - FINAL Partial Approval -need two heads in ultrasound room
-need head in OR corridor
-static and residual preseeure in system is low
-need pressure relief valve

-need more coverage in mechanical hallway
03/12/2020 FIRE SPKLR - FINAL Cancelled IVRS - RI canceled