Permit: T19FC00699

Parcel: 12404100B


Addresses:

930 E 2ND ST


Inspection Status: Approved

Inspection History: FIRE PUMP - FINAL

Permit Number - T19FC00699

Inspection Description - FIRE PUMP - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
11/17/2020 FIRE PUMP - FINAL Approved
03/11/2020 FIRE PUMP - FINAL Partial Approval Tested the fire pump on temporary power. Pump passed the curve test. Need to verify waterflow with the generator and confirm signals to the FACP once that is installed. Pump is active and we can have water flow from the building.