Permit: T19FC00699

Parcel: 12404100B


Addresses:

930 E 2ND ST

Inspection Status: Approved

Inspection History: FIRE SPKLR - OH PIPING & HYDRO

Date Description Inspector Results Comments
11/17/2020 FIRE SPKLR - OH PIPING & HYDRO Approved
05/28/2020 FIRE SPKLR - OH PIPING & HYDRO Partial Approval 14th Floor OH/Hydro Piping Test. 223psi.
05/21/2020 FIRE SPKLR - OH PIPING & HYDRO Partial Approval 13th Floor OH/Hydro Piping Test. 217psi.
05/08/2020 FIRE SPKLR - OH PIPING & HYDRO Partial Approval 11th floor partial. OH/Hydro test approved on residential, burn side only.
05/05/2020 FIRE SPKLR - OH PIPING & HYDRO Partial Approval 10th Floor OH/Hydro Piping Test. 220psi. For piping replacement in Fire Damage area only.
04/30/2020 FIRE SPKLR - OH PIPING & HYDRO Partial Approval 9th Floor OH/Hydro Piping Test. 215psi. For piping replacement in Fire Damage area only.
04/22/2020 FIRE SPKLR - OH PIPING & HYDRO Partial Approval 8th Floor OH/Hydro Piping Test. 209psi. For Fire Damage area only.
04/14/2020 FIRE SPKLR - OH PIPING & HYDRO Partial Approval 12th Floor OH/Hydro Piping Test. 227psi.
04/14/2020 FIRE SPKLR - OH PIPING & HYDRO Partial Approval 6th Floor OH/Hydro Piping Test. 210psi. For Piping replacement in Fire Damage area only.
04/06/2020 FIRE SPKLR - OH PIPING & HYDRO Partial Approval 5th Floor OH/Hydro Piping Test. 219psi. For Piping replacement in Fire Damage area only.
03/24/2020 FIRE SPKLR - OH PIPING & HYDRO Partial Approval 4th Floor OH/Hydro Piping Test. 220psi. For Piping replacement in Fire Damage area only.
03/24/2020 FIRE SPKLR - OH PIPING & HYDRO Partial Approval 11th Floor OH/Hydro Piping Test. 205psi. Included all Plastic Pipe. Steel piping will be tested at a later date.
03/16/2020 FIRE SPKLR - OH PIPING & HYDRO Partial Approval 10th Floor OH/Hydro Piping Test. 215psi. Included all Plastic Pipe. Steel piping above previous fire damage will be tested at a later time.
03/06/2020 FIRE SPKLR - OH PIPING & HYDRO Partial Approval 9th floor partial OH/Hydro @ 213 PSI
03/04/2020 FIRE SPKLR - OH PIPING & HYDRO Partial Approval 8th floor OH/Hydro @214 PSI
02/20/2020 FIRE SPKLR - OH PIPING & HYDRO Partial Approval 7th Floor OH/Hydro Piping Test. 215psi.
02/13/2020 FIRE SPKLR - OH PIPING & HYDRO Partial Approval 6th Floor OH/Hydro Piping Test. 205psi.
02/05/2020 FIRE SPKLR - OH PIPING & HYDRO Partial Approval 5th Floor OH/Hydro Piping Test. 225psi.
01/15/2020 FIRE SPKLR - OH PIPING & HYDRO Partial Approval 4th Floor OH/Hydro Piping Test. 200psi. Includes everything except fire damage area that will be replaced and tested separately.
12/19/2019 FIRE SPKLR - OH PIPING & HYDRO Partial Approval 3rd Floor OH/Hydro Piping Test. 210 PSI.