Inspection History Details
Inspection Status: Approved
Inspection History: FIRE SPKLR - OH PIPING & HYDRO
Permit Number - T19FC00699
Inspection Description - FIRE SPKLR - OH PIPING & HYDRO
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/17/2020 | FIRE SPKLR - OH PIPING & HYDRO | Approved | ||
05/28/2020 | FIRE SPKLR - OH PIPING & HYDRO | Partial Approval | 14th Floor OH/Hydro Piping Test. 223psi. | |
05/21/2020 | FIRE SPKLR - OH PIPING & HYDRO | Partial Approval | 13th Floor OH/Hydro Piping Test. 217psi. | |
05/08/2020 | FIRE SPKLR - OH PIPING & HYDRO | Partial Approval | 11th floor partial. OH/Hydro test approved on residential, burn side only. | |
05/05/2020 | FIRE SPKLR - OH PIPING & HYDRO | Partial Approval | 10th Floor OH/Hydro Piping Test. 220psi. For piping replacement in Fire Damage area only. | |
04/30/2020 | FIRE SPKLR - OH PIPING & HYDRO | Partial Approval | 9th Floor OH/Hydro Piping Test. 215psi. For piping replacement in Fire Damage area only. | |
04/22/2020 | FIRE SPKLR - OH PIPING & HYDRO | Partial Approval | 8th Floor OH/Hydro Piping Test. 209psi. For Fire Damage area only. | |
04/14/2020 | FIRE SPKLR - OH PIPING & HYDRO | Partial Approval | 12th Floor OH/Hydro Piping Test. 227psi. | |
04/14/2020 | FIRE SPKLR - OH PIPING & HYDRO | Partial Approval | 6th Floor OH/Hydro Piping Test. 210psi. For Piping replacement in Fire Damage area only. | |
04/06/2020 | FIRE SPKLR - OH PIPING & HYDRO | Partial Approval | 5th Floor OH/Hydro Piping Test. 219psi. For Piping replacement in Fire Damage area only. | |
03/24/2020 | FIRE SPKLR - OH PIPING & HYDRO | Partial Approval | 4th Floor OH/Hydro Piping Test. 220psi. For Piping replacement in Fire Damage area only. | |
03/24/2020 | FIRE SPKLR - OH PIPING & HYDRO | Partial Approval | 11th Floor OH/Hydro Piping Test. 205psi. Included all Plastic Pipe. Steel piping will be tested at a later date. | |
03/16/2020 | FIRE SPKLR - OH PIPING & HYDRO | Partial Approval | 10th Floor OH/Hydro Piping Test. 215psi. Included all Plastic Pipe. Steel piping above previous fire damage will be tested at a later time. | |
03/06/2020 | FIRE SPKLR - OH PIPING & HYDRO | Partial Approval | 9th floor partial OH/Hydro @ 213 PSI | |
03/04/2020 | FIRE SPKLR - OH PIPING & HYDRO | Partial Approval | 8th floor OH/Hydro @214 PSI | |
02/20/2020 | FIRE SPKLR - OH PIPING & HYDRO | Partial Approval | 7th Floor OH/Hydro Piping Test. 215psi. | |
02/13/2020 | FIRE SPKLR - OH PIPING & HYDRO | Partial Approval | 6th Floor OH/Hydro Piping Test. 205psi. | |
02/05/2020 | FIRE SPKLR - OH PIPING & HYDRO | Partial Approval | 5th Floor OH/Hydro Piping Test. 225psi. | |
01/15/2020 | FIRE SPKLR - OH PIPING & HYDRO | Partial Approval | 4th Floor OH/Hydro Piping Test. 200psi. Includes everything except fire damage area that will be replaced and tested separately. | |
12/19/2019 | FIRE SPKLR - OH PIPING & HYDRO | Partial Approval | 3rd Floor OH/Hydro Piping Test. 210 PSI. |