Permit: T19FC00667

Parcel: 132041320


Addresses:

3361 E 36TH ST


Inspection Status: Approved

Inspection History: FIRE - ALARM FINAL

Permit Number - T19FC00667

Inspection Description - FIRE - ALARM FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
09/19/2019 FIRE - ALARM FINAL Approved
09/17/2019 FIRE - ALARM FINAL Denied HVAC units did not shut down upon duct detector activation

Tested -
-pull station
-smoke detector
-sprinkler flow switch
-sprinkler tamper
-5 duct detectors transmitted to panel

-Need NFPA 72 ROC paperwork upon completion