Inspection Status: Approved
Inspection History: FIRE - ALARM FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/19/2019 | FIRE - ALARM FINAL | Approved | ||
| 09/17/2019 | FIRE - ALARM FINAL | Denied | HVAC units did not shut down upon duct detector activation Tested - -pull station -smoke detector -sprinkler flow switch -sprinkler tamper -5 duct detectors transmitted to panel -Need NFPA 72 ROC paperwork upon completion |