Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - ALARM FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/04/2019 | FIRE - ALARM FINAL | Approved | ||
| 08/21/2019 | FIRE - ALARM FINAL | Denied | Shall have two forms of transmission. Only one phone line is permitted per NFPA 72 reference 26.6.1.4 Shall have red fire alarm lock for panel. Shall have the batteries labeled with dates. |