Permit: T19FC00457

Parcel: 116206300

Inspection Status: Approved

Inspection History: FIRE SPKLR - OH PIPING & HYDRO

Permit Number - T19FC00457

Inspection Description - FIRE SPKLR - OH PIPING & HYDRO

Inspection Status - Approved

Date Description Inspector Results Comments
11/17/2020 FIRE SPKLR - OH PIPING & HYDRO Approved Inspection 6 - All areas inspected
10/09/2020 FIRE SPKLR - OH PIPING & HYDRO Cancelled IVRS - RI canceled
04/09/2020 FIRE SPKLR - OH PIPING & HYDRO Partial Approval Inspection 5 - 4th floor south side residential areas - partial approval. Add sprinkler coverage in concealed cumbustible space.
03/27/2020 FIRE SPKLR - OH PIPING & HYDRO Partial Approval Inspection 4 - partial 4th floor residential areas. Upright coverage needed in northwest unit.
03/05/2020 FIRE SPKLR - OH PIPING & HYDRO Partial Approval Inspection 3 - 3rd floor residential areas - partial approval. Ok to instlall insulation and shetrock deck.
-A couple concealed spaces found with no coverage, noted on plans.
- One head too far off wall, noted on plan.
02/13/2020 FIRE SPKLR - OH PIPING & HYDRO Partial Approval Inspection 2 - 2nd floor residential areas - partial approved. Ok to install insulation and sheetrock at roof deck.
Elevator vestibule dropped ceiling area is greater than on plan, sprinkler coverage or insulation required.
Concealed combustible spaces noted on plan need to have sprinkler head added.
02/06/2020 FIRE SPKLR - OH PIPING & HYDRO Partial Approval Inspection 1 - 1st floor residential areas - partial
OK, to install insulation and sheetrock at roof deck.
-comercial areas still to be tested.
-ensure ceiling fans do not cause obstruction to sprinkler heads
-Concealed combustible spaces need to be sheetrocked, filled with insulation or have sprinkler coverage - 3 mailbox niches in 1st floor hallway.
- Interstitial spaces between dropped ceiling and roof deck also constitute a concealed combustible space.