Inspection History Details
Inspection Status: Approved
Inspection History: FIRE SPKLR - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/24/2019 | FIRE SPKLR - FINAL | Approved | ||
| 12/19/2019 | FIRE SPKLR - FINAL | Partial Approval | -label inspectors test valve -inspectors test needs to be installed after flow switch. -secure FDC pipe. |
|
| 12/04/2019 | FIRE SPKLR - FINAL | Cancelled | cancelled. cannot final until FA is complete. | |
| 11/21/2019 | FIRE SPKLR - FINAL | Cancelled | -Cancelled by contractor | |
| 11/08/2019 | FIRE SPKLR - FINAL | Denied | nobody on site. no message. no appointment. reinspection fee added. must be paid prior to final. |