Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - ALARM FINAL
Permit Number - T19FC00438
Inspection Description - FIRE - ALARM FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/17/2019 | FIRE - ALARM FINAL | Approved | tested duct smokes 2-4 7&6 and confirmed that they worked properly. Fire alarm program was changed and they are programmed as a supervisory now and not an alarm. Need as built fire alarm drawings to close out fire alarm permit | |
09/12/2019 | FIRE - ALARM FINAL | Partial Approval | Waterflow was at 49 seconds. Tested, manual pull, smoke above panel, duct smoke detectors, water flows and tampers. Confirmed signals to the offsite fire alarm monitoring. Duct smoke 4 and 2 need to be changed at the unit Duct 6 & 7 need to be tested once they are proggramed Need RED Fire alarm lock out on the breaker and FACP labeled with the disconnecting means Duct smokes need to be programmed as a supervisory per code not a general alarm and re-tested Need 2 fire alarm monitoring permits Pay re-inspection fee prior to calling back in Need to submit asbuilt drawings |