Permit: T19FC00409

Parcel: 128010040


Addresses:

5950 E BROADWAY BL


Inspection Status: Approved

Inspection History: FIRE - ALARM FINAL

Permit Number - T19FC00409

Inspection Description - FIRE - ALARM FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
10/08/2019 FIRE - ALARM FINAL Approved -NFPA 72 ROC paperwork will be submitted at the fire alarm inspection for the TI. Permit T19FC00816
09/06/2019 FIRE - ALARM FINAL Partial Approval -need 72 record of completion
-cannot have two phone lines. need second means of that is not a phone line.
-need separate permit for monitoring.
05/31/2019 FIRE - ALARM FINAL Correction Required THIS IS A FACP FOR THE SHELL. MONITORING REQUIRES A PERMIT.
NO NOTIFICATION APPLIANCES WILL BE INSTALLED SINCE A VOICE EVAC SYSTEM WILL SOON BE REQUIRED