Permit: T19FC00303

Parcel: 12314007B


Addresses:

2001 N PARK AV


Inspection Status: Approved

Inspection History: FIRE - ALARM FINAL

Permit Number - T19FC00303

Inspection Description - FIRE - ALARM FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
11/25/2020 FIRE - ALARM FINAL Approved
11/18/2020 FIRE - ALARM FINAL Cancelled IVRS - RI canceled
12/10/2019 FIRE - ALARM FINAL Denied 1) Add notification device to charting room 1st floor
2) Add notification device to Social Services
3) Add notification device to Admin Office
4) Add notification device to 1st floor conference room
5) Add notification device 1st and 2nd floor all 4 medication rooms
6) Add notifiication device 1st floor residence living
7) Add notification device to laundry and storage rooms
8) Add notification device to the mechanical and back storage areas
9) Add notification device to the MDS office
10) Add a smoke to the small hall by the bathrooms in the pocket areas
11) Add smoke by the lounge pocket
12) Smoke outside MDS too close to the register x 2
13) Add notification device 2nd floor beauty shop
14) Add notification device 2nd floor shared office
15) Add notification device 2nd floor south restroom
16) check beam pockets on the 2nd floor for smoke detector coverage
17) Change the FACP program so that the doors do NOT re-latch on a silence only when the fire alarm system is reset
18) Pull a permit for fire alarm monitoring
19) Submit Asbuilt drawings and pay the applicable fees
20) Add notification device to the 2nd floor conference room
21) Add notification device to the 2nd floor HR department