Permit: T19FC00261

Parcel: 121093720


Addresses:

2121 N CRAYCROFT RD


Inspection Status: Approved

Inspection History: FIRE - ALARM FINAL

Permit Number - T19FC00261

Inspection Description - FIRE - ALARM FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
07/26/2019 FIRE - ALARM FINAL Approved
07/25/2019 FIRE - ALARM FINAL Cancelled IVRS - AP canceled
07/25/2019 FIRE - ALARM FINAL Partial Approval Two separate means of transmission required - two phone lines is not allowed.
07/24/2019 FIRE - ALARM FINAL Cancelled IVRS - AP canceled
04/25/2019 FIRE - ALARM FINAL Compliance IF THE FACP HAS A DACT IT WILL REQUIRE 2 MEANS OF TRANSMISSION