Permit: T19FC00251

Parcel: 140260430

Inspection Status: Approved

Inspection History: FIRE - ALARM FINAL

Permit Number - T19FC00251

Inspection Description - FIRE - ALARM FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
07/12/2019 FIRE - ALARM FINAL Approved
07/01/2019 FIRE - ALARM FINAL Partial Approval Need to correct the blue horn strobes
Add the three missing duct detectors
Pay re-inspection fee
04/23/2019 FIRE - ALARM FINAL Partial Approval Phase 1 completed. Tested the following:
Pre-action alarm, supervisory and trouble
Clean Agent Alarm, supervisory and trouble
2 flow switches, 3 tamper switches.
Confirmed the monitoring with Central Alarm. This was the second inspection. Advised Mark that fees will be added.