Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - ALARM FINAL
Permit Number - T19FC00199
Inspection Description - FIRE - ALARM FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/17/2021 | FIRE - ALARM FINAL | Approved | Fire alarm was complete on CM under 434 E University | |
12/19/2019 | FIRE - ALARM FINAL | Partial Approval | two way communication approved. panel in "trouble" phone line 2. RI fees added to permit. |
|
12/06/2019 | FIRE - ALARM FINAL | Partial Approval | Fire alarm is approved Need to correct the A phone and the dispatch numbers |
|
11/27/2019 | FIRE - ALARM FINAL | Partial Approval | Acceptance test conducted. Elevator in compliance. List of outstanding items: -Obtain permit for monitoring. -Need as builts approved and all fees paid. -Provide locking/secure box around transformer plug from teleguard communicator to outlet. -Tamper switch on 2nd floor reporting as water flow. This was resolved and retested while on site. -Work room on plans wants horn/strobe in center of room. -Replace strobe only in NE office with horn/strobe as indicated on plans. -Need to test comm failures. -Provide record of completion. -Update TFD fire dispatch phone number with central station. -Two way communication on 3rd floor not working. |
|
11/25/2019 | FIRE - ALARM FINAL | Cancelled | Cancelled by contractor | |
10/11/2019 | FIRE - ALARM FINAL | Cancelled | IVRS - RI canceled | |
10/11/2019 | FIRE - ALARM FINAL | Partial Approval | Need to remove the duct smokes from the plns and add to each TI Submit asbuilt drawings and show that you are monitoring the system 1 dialer needs to be replaced with a AT&T cell Need RED Fire alarm lock outs on breakers |
|
04/08/2019 | FIRE - ALARM FINAL | Cancelled | MONITORING REQUIRES A PERMIT NEED ASBUILT DRAWINGS PRIOR TO CALLING IN FINAL ADD NOTIFICATION DEVICES TO OPEN SPACES PER NFPA 72 |