Permit: T19FC00193

Parcel: 12108065F


Addresses:

1401 N ROOK AV

Inspection Status: Approved

Inspection History: FIRE SPKLR - FINAL

Date Description Inspector Results Comments
08/01/2019 FIRE SPKLR - FINAL Approved
03/19/2019 FIRE SPKLR - FINAL Partial Approval 1. clean all mud off sprink heads in all rooms or replace.
2. need to visualize pipe. cut hole in ceiling.
3. heads need to be extended/dropped. two layers of drywall were added which caused the heads needing to be extended.
-While on site, contractor provided picture showing pipe. I will accept this. No need to open ceiling this time.