Inspection Status: Passed
Inspection History: COT - FCON - Sprinkler - Final
| Date |
Description |
Inspector |
Results |
Comments |
| 11/08/2019 |
COT - FCON - Sprinkler - Final |
JPEELDAVIS |
Approved |
Entered by JPEELDA1 - Riser A 49 Seconds confirmed to fire alarm
Riser B 56 Seconds confirmed to fire alarm
Riser C 51 Seconds confirmed to fire alarm
Riser D 49 Seconds confirmed to fire alarm
Riser E 48 Seconds confirmed to fire alarm |