Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T19FC00027

Parcel: 11703319A


Addresses:

434 E UNIVERSITY BL


Inspection Status: Approved

Inspection History: FIRE SPKLR - UG PIPING FLUSH

Permit Number - T19FC00027

Inspection Description - FIRE SPKLR - UG PIPING FLUSH

Inspection Status - Approved

Date Description Inspector Results Comments
03/05/2019 FIRE SPKLR - UG PIPING FLUSH Approved
02/08/2019 FIRE SPKLR - UG PIPING FLUSH Denied -wanted to flush a 6" line with 2" reducer. advised we wanted 3" minimum for flush.
-provide record of completion after flush.