Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 07/19/2019 |
ELECTRIC - FINAL |
|
Approved |
bushing needed at back of panel. |
| 07/18/2019 |
ELECTRIC - FINAL |
|
Not ready for Inspection |
still need to verify wiring size per previous correction, panel still needs to be labeled, please call inspection back in. |
| 07/17/2019 |
ELECTRIC - FINAL |
|
Not ready for Inspection |
panel wired in aluminum wiring this is causing the wiring to be undersized. Please follow chart E3705.1 in the IRC on minimum conductor sizes. Also panel will need to be labeled at final inspection. |