Inspection History: ELECTRIC - SERVICE UPGRADE

Permit Number - T19EL00101

Inspection Description - ELECTRIC - SERVICE UPGRADE

Inspection Status - Approved

Date Description Inspector Results Comments
04/24/2019 ELECTRIC - SERVICE UPGRADE Approved Clear incr
04/23/2019 ELECTRIC - SERVICE UPGRADE Correction Required Existing UFER’s must pass. 25 OHMs resistance to ground test or 2-8’ ground rods must be installed per COT with NEC Standards.
A water bond the same size as the GEC must also be installed.
For an electrical final all circuit must also be permanently labeled.
As discussed on site the house has no gas.
When all completed recall this inspection.
04/22/2019 ELECTRIC - SERVICE UPGRADE Not ready for Inspection Work is not complete enough to inspect.