Case: T19DV07581

Parcel: 110080680

Inspection Status: Approved

Inspection History: INSP - INITIAL CODE ENFORCMENT

Date Description Inspector Results Comments
10/07/2019 INSP - INITIAL CODE ENFORCMENT Approved FRONT ADDITION IS BEING UTILIZED AS LIVING SPACE. RESEARCH FOUND THE ADDITION WAS BUILT BETWEEN 1998 AND 2002. FOUND NO PERMITS IN THE SYSTEM.
WOOD FRAME CONSTRUCTION ADDITION IS BUILT TO THE PROPERTY LINE, POSSIBLY OVER THE PROPERTY LINE, PER AERIAL PHOTOS, AND IS ATTACHED TO ANOTHER STRUCTURE AT THE NEIGHBORING PROPERTY RESULTING IN NO FIRE BREAK
ADDITION HAS A UTILITY CLOSET PLUMBING FIXTURES INSTALLED FOR A WASHER
ADDITION FLOORING IS COMPOSED OF BRICK PAVERS WHICH ARE EXTREMELY UNEVEN POSING A TRIP HAZARD. FLOORING IS NOT SEALED OR GROUTED IN ANY WAY
WINDOW STYLE A/C UNIT INSTALLED AT THE FRONT OF THE ADDITION IS NOT SECURED WHICH ALLOWS WATER TO PENETRATE THE WALL FROM THE EXTERIOR. A/C UNIT COILS ARE EXTREMELY DIRTY AND REQUIRES SERVICE
REAR DOOR TO ADDITION IS SECURED WITH A SLIDE LATCH WHICH COULD POSE AN EMERGENCY EXIT HAZARD. REQUIRES A PROPER LOCKING MECHANISM
ADDITION HAS MAIN ELECTRICAL PANEL IN THE INTERIOR WITH NO MAIN SHUT OFF, NO LABELING, MISSING BLANKS.
2- 220 OUTLETS INSTALLED IN THE FRONT ADDTION. TESTED UNENERGIZED
MAIN LIVING SPACE DOOR AND FRAME OR EXTREMELY DETERIORATED
KITCHEN LACKS PROPER OUTLETS WITH ONE OUTLET PARTIALLY COVERED
FRIGERATOR HAS EXPOSED WIRING COMING FROM THE METAL HINGE POSING A SHOCK HAZARD. IS ALSO PLUGGED INTO A UNAPPROVED PLASTIC MUTI PLUG WHICH MAY BE DANGEROUS DUE TO OVERHEATING. PLUG WIRING IS EXPOSED AND NOT SECURED
BATHROOM LACKS ELECTRICAL OUTLET.
OPEN GROUND AND REVERSED NEUTRAL WIRING THROUGHOUT THE UNIT AS WELL AS UNSECURED OUTLETS
WATER HEATER INSTALLED IN THE KITCHEN IS COMPLETELY
BLOCKED BY THE REFRIGERATOR WITH NO ACCESS IN CASE OF EMERGENCY
WALL HEATER LACKS THERMOSTAT. UNABLE TO TEST IF OPERATIONAL
OPEN ELECTRICAL JUNCTION BOX ON THE NORTH WALL. WIRES ARE NOT CAPPED AND ARE EXPOSED
ROOF SYSTEM ON THE NORTH SIDE IS DETERIORATED AND ROTTED
BROKEN WINDOW PANELS THROUGHOUT THE UNIT
KITCHEN SINK LACK PROPER SHUT OFF VALVES