Case: T19DV07410

Parcel: 138144510

Inspection Status: Approved

Inspection History: INSP - INITIAL CODE ENFORCMENT

Case Number - T19DV07410

Inspection Description - INSP - INITIAL CODE ENFORCMENT

Inspection Status - Approved

Date Description Inspector Results Comments
09/21/2019 INSP - INITIAL CODE ENFORCMENT Approved T.P.D. on site with min. housing condition. Arrived and the units still on site. Did meet with the tenants and was able to do an inspection. The gas meter has been pinned due to leaks in the pipe feeding the unit, the gas furnace has a dryer vent pipe on the vent pipe to the venting system, the water heater has been replaced with new and not installed properly, lacking drain line for TPR valve, Gas lacking the sediment trap, has over 6' of flex line for cold water supply, kitchen and bathroom outlets by the sink areas not GFCI protected, kitchen sink has reversed pitch drain pipe, the smoke detectors in the bedrooms are at wrong location, the windows need new rolleres, some were screwed shut and the screws were removed at the time of the inspection, open ground on grounded outlets amd may be on a 2-wire system, globes are lacking, the exterior doors not locking properly, the storage room door on the exterior is lacking a lock. The gas meter is tagged by Southwest gas. Will contact management and will check on Monday about moving to another unit. RV.