Case: T19DV05773

Parcel: 12215239B


Addresses:

3414 E GRANT RD #2


Inspection Status: Approved

Inspection History: INSP - INITIAL CODE ENFORCMENT

Case Number - T19DV05773

Inspection Description - INSP - INITIAL CODE ENFORCMENT

Inspection Status - Approved

Date Description Inspector Results Comments
07/18/2019 INSP - INITIAL CODE ENFORCMENT Approved EMERGENCY CALL OUT BY TEP, UNIT 2 MAIN DISCONNECT WAS FOUND BY TEP BEING ENERGIZED BY UNIT 1 MAIN DISCONNECT, A 50 AMP CIRCUIT BREAKER WAS PROVIDING POWER BY A NUMBER 10 CONDUCTOR TO THE UNIT 2 MAIN DISCONNECT. TODAYS INSPECTION FOUND A BRANCH CIRCUIT FROM UNIT 1 MAIN DISCONNECT WHICH LEADS TO A JUNCTION BOX AND THEN TO BRANCHES OFF TO UNIT 2 MAIN DISCONNECT AND DOWNSTREAM EQUIPMENT.THE OVERCURRENT PROTECTION EXCEEDS THE AMPACITY OF THE CONDUCTORS
BOTH SERVICES ARE SHARE LIVE CONDUCTORS AND PREVIOUS TAMPERING IDENTIFIED BY TEP ARE HAZARDS. THE POWER WAS ORDER TO BE DISCONNECTED AND THE UNIT WAS CONDEMNED UNFIT TO OCCUPY. PERMITS ARE REQUIRED FOR REPAIRS. DAY TIME ACCESS ONLY FOR REMOVAL OF PERSONNEL ITEMS. OWNER WAS ADVISED IF THIS ORDER IS VIOLATED THEN BOARDING THE ENTIRE BUILDING WILL BE ORDERED.