Case: T19DV05771

Parcel: 12215239B


Addresses:

3414 E GRANT RD #1


Inspection Status: Approved

Inspection History: INSP - INITIAL CODE ENFORCMENT

Case Number - T19DV05771

Inspection Description - INSP - INITIAL CODE ENFORCMENT

Inspection Status - Approved

Date Description Inspector Results Comments
07/18/2019 INSP - INITIAL CODE ENFORCMENT Approved EMERGENCY CALL OUT BY TEP, UNIT 1 MAIN DISCONNECT HAD POWER DISCONNECT BY REMOVING THE METER, IN FEB 2018. ON 7-15-2019 TEP FOUND THE SERVICE BEING ENERGIZED BY METAL BARS. THERE WAS ALSO A 50 AMP CIRCUIT BREAKER WHICH WAS PROVIDING POWER BY A NUMBER 10 CONDUCTOR TO THE UNIT 2 MAIN DISCONNECT. TEP DID REMOVE THE METAL BARS AND INSTALL A BLANK COVER.
TODAY INSPECTION FOUND A 50 AMP CIRCUIT BREAKER WHICH WAS PROVIDING POWER BY A NUMBER 10 CONDUCTOR TO A JUNCTION BOX WITH ONE 20 AMP DUPLEX RECEPTACLE AND ONE 30 AMP RECEPTACLE. THERE ALSO A 30 AMP CIRCUIT BREAKER WHICH HAS A NUMBER 12 CONDUCTOR WHICH FEEDS A JUNCTION BOX WHICH IS SHARED WITH MAIN DISCONNECT UNIT 2. THE OVERCURRENT PROTECTION EXCEEDS THE AMPACITY OF THE CONDUCTORS
UNAPPROVED WIRING METHODS AND PREVIOUS TAMPERING IDENTIFIED BY TEP ARE HAZARDS. THE POWER WAS ORDER TO BE DISCONNECTED AND THE UNIT WAS CONDEMNED UNFIT TO OCCUPY. PERMITS ARE REQUIRED FOR REPAIRS. DAY TIME ACCESS ONLY FOR REMOVAL OF PERSONNEL ITEMS. OWNER WAS ADVISED IF THIS ORDER IS VIOLATED THEN BOARDING THE ENTIRE BUILDING WILL BE ORDERED.