Inspection History Details
Inspection Status: Approved
Inspection History: INSP - INITIAL CODE ENFORCMENT
Case Number - T19DV05101
Inspection Description - INSP - INITIAL CODE ENFORCMENT
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/07/2019 | INSP - INITIAL CODE ENFORCMENT | Approved | ON 06-07-2019 THERE WAS A FIRE DAMAGE TO BUILDING 14. THE REAR LOADING DOCK AREA'S ROOF ASSEMBLY HAS COLLAPSED INBOARD. THIS AREA IS ESTIMATED AT 50 FEET X 80 FEET. THE BUILDING HAS BLOCK WALLS. THERE IS A GLULAM BEAM WHICH RUNS 50 FEET, THIS BEAM HAS DEEP CRACKING AND IS PARTIALLY CHARRED. LATER THAT DAY TUCSON POLICE ORDERED A RECOVERY OPERATION TO LOOK FOR BODIES. A CONTRACTOR WITH A LARGE EXCAVATOR WAS CALLED TO THE SITE TO MOVE ALL THE RUBBLE SO THAT THE INVESTIGATORS COULD SIFT THROUGH THE RUBBLE. DURING THIS PROCESS THE EXCAVATOR CREATED A LARGE OPENING IN THE SOUTH WALL OF 25 FEET BY THE HEIGHT OF THE BUILDING. THE SOUTH WALL AND A PORTION OF THE WEST WALL WHICH HAS TWO BAY DOORS IS NOT STABLE AND CAN NO LONGER SUPPORT ITS OWN WEIGHT OR WITH STAND HIGH WINDS. THE SOUTHWEST CORNER OF THE LOADING DOCK WITH NO ROOF ASSEMBLY AND THE LARGE DAMAGED OPENING MUST BE DEMOLISHED. |