Inspection History Details
Inspection Status: Approved
Inspection History: INSP - INITIAL CODE ENFORCMENT
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/17/2019 | INSP - INITIAL CODE ENFORCMENT | Approved | VISITED SITE FOR A CAR INTO BUILDING AT 3379 E WATER ST, UPON ARRIVAL FOUND STRUCTURE WAS A TRIPLEX, UNITS INDIVIDUALLY ADDRESSED. CAR HIT THE BUILDING RIGHT AT THE ELECTRICAL SERVICE (3-PACK) PANEL THAT FEEDS ALL THREE UNITS. PANEL FELL OF THE WALL, ARCHING KILLED POWER TO ALL THREE UNITS AND EVENTUALLY TEP HAD CUT POWER AT THE POLE AND REMOVED THE METERS. MY FINDINGS ARE AS FOLLOWS: BUILDING: >5-6 2X6 STUDS DISPLACED FROM BOTTOM PLATE, 3 STUDS ON THE EAST WALL AND A CORNER RETURN ON THE NORTH WALL. >PLYWOOD SHEAR ALSO DAMAGED ON THE CORNER. > 5FT X 8 FT HOLE IN THE STUCCO OF THE EAST WALL AND 4 FT X 8FT HOLE ON THE NORTH WALL. > DRYWALL DAMAGED ON THE WALLS INSIDE APPROX 7 FT X 8 FT OF DRYWALL. ELECTRICAL: >3-PACK SERVICE PANEL LEFT HANGING FROM THE WALL. POWER CUT AT THE POLE, RECONNECT PERMIT REQUIRED FOR 3375, 3377 AND 3379. TEP STATED NEW SERVICE LINE FROM THE POLE WILL ALSO BE REQUIRED >INTERIOR WIRING STRECHED INSIDE THE WALL AND ONE OUTLET DAMAGED. NO PLUMBING OR MECHANICAL DAMAGE. OCCUPANT CYNTHIA HERNANDEZ INFORMTED ME SHE WAS SECTION 8 BUT WOULD NOT REQUIRE HOUSING AS SHE WOULD BE STAYING WITH A FRIEND DOWN THE STREET. BONNIE WITH SECTION 8 WAS INFORMED OF THE INNCIDENT, BONNIE STATED SHE WOULD CONTACT SECTION 8, LET THEM >OWNER WAS CONTACTED AND ARRIVED ON SITE. PERSON IN THE CAR LEFT THE SCENCE BUT WAS FOUND BY TPD. ARCADIAN IND. WAS CONTACTED TO SECURE THE HOLE LEFT IN THE WALL (2 SHEETS) OWNER WAS ISSUED EMERGENCY VACATE NOV WHICH INCLUDED PERMITS REQUIRED FOR ALL REPAIRS. COMPLIANCE/ CLOSE CASE. |