Case: T19DV03957

Parcel: 115060150


Addresses:

255 W FLORES ST


Inspection Status: Approved

Inspection History: INSP - FOLLOW UP CODE ENFORCE

Case Number - T19DV03957

Inspection Description - INSP - FOLLOW UP CODE ENFORCE

Inspection Status - Approved

Date Description Inspector Results Comments
02/25/2020 INSP - FOLLOW UP CODE ENFORCE Approved CERTIFICATE OF OCCUPANCY HAS BEEN ISSUED 2/6/2020 CLOSING CASE.
12/16/2019 INSP - FOLLOW UP CODE ENFORCE Approved PERMIT T19BU00601 HAS BEEN FINAL FOR THE DEMOLITION OF THE SWIMMING POOL.
08/19/2019 INSP - FOLLOW UP CODE ENFORCE Approved ON SITE MEETING REQUESTED BY PREVIOUS OWNER AND HIS CONTRACTOR, E.S. DIRECTOR, CODE ENFORCEMENT SUPERVISOR, CHIEF BUILDING OFFICIAL, AND CURRENT PROPERTY MANAGER. AT THE MEETING IT HAS BEEN ACKNOWLEDGED THE NOTICE HAS BEEN RECEIVED BY THE NEW OWNER AND IS AWARE OF THE TIMELINE.
08/12/2019 INSP - FOLLOW UP CODE ENFORCE Approved ON SITE BUILDING SAFETY INSPECTION WITH OTHER CITY DEPARTMENTS

PENDING VIOLATIONS TO BE ABATED FROM ORIGINAL NOTICE OF VIOLATION: ELECTRICAL ENCLOSURES ARE NOT PROTECTED AND ARE NOT WEATHER TIGHT. NON METALLIC SHEATHED CABLE BEING USED OUTDOORS UNDER EAVE AREA NOT PROTECTED. OUTDOOR LIGHTING THAT WAS PREVIOUSLY ENERGIZED WITH A SERIES OF EXTENSION CORDS IN AN UNAPPROVED WIRING METHOD THAT IS CURRENT STILL ATTACHED TO THE FRONT OF THE BUILDING DOES NOT MEET THE 2012 OUTDOOR LIGHTING CODE. NO CURRENT CERTIFICATE OF OCCUPANCY HAS BEEN OBTAINED. PERMIT T19CM04365 REMAINS IN ISSUED STATUS FOR AN ADA REMODEL. NO PERMIT FOR THE REQUIRED CODE COMPLIANT POOL BARRIER HAS BEEN OBTAINED.
07/09/2019 INSP - FOLLOW UP CODE ENFORCE Approved CARPORT HAS BEEN REMOVED, NON METALLIC SHEATHED CABLE BEING USED OUTDOORS UNDER EAVE AREA NOT PROTECTED. OUTDOOR LIGHTING THAT WAS PREVIOUSLY ENERGIZED WITH A SERIES OF EXTENSION CORDS IN AN UNAPROVED WIRING METHOD THAT IS CURRENT STILL ATTACHED TO THE FRONT OF THE BUILDING DOES NOT MEET THE 2012 OUTDOOR LIGHTING CODE. NO CURRENT CERTIFICATE OF OCCUPANCY HAS BEEN OBTAINED. PERMIT T19CM04365 HAS BEEN ISSUED FOR AN ADA REMODEL.
05/31/2019 INSP - FOLLOW UP CODE ENFORCE Approved COMMONWEALTH ELECTRIC COMPANY ON SITE WITH PROPERTY OWNER TO REVIEW NOTICE OF VIOLATION.
05/29/2019 INSP - FOLLOW UP CODE ENFORCE Approved ONSITE INSPECTION: THERE IS NO CURRENT CERTIFICATE OF OCCUPANCY OR APPROVALS FROM THE CITY OF TUCSON FOR THE CURRENT USE WHICH IS RESIDENTIAL APARTMENT RENTALS. THE LAST APPROVED CERTIFICATE OF OCCUPANCY WAS ISSUED IN MAY 14, 1992 FOR RESIDENTIAL CARE/ HALFWAY HOUSE.
THERE ARE MULTIPLE POSTS TO THE REAR ATTACHED CARPORT. THE CARPORT'S CONSTRUCTED IS STEEL POSTS AND WOOD FRAMING MEMBERS. THERE IS MISSING HARDWARE THAT CONNECTS THE POSTS TO THE BEAMS. THE CARPORT'S POST IN FRONT OF UNIT 10 HAS WOOD BLOCKS IN BETWEEN ITSELF AND THE BEAM, THIS IS DUE TO POST DAMAGE. THERE IS NO POSITIVE CONNECTION AT THIS POINT.

THERE ARE MULTIPLE UNUSED OPENINGS ON THE ELECTRICAL SERVICE EQUIPMENT AND OTHER ENCLOSURES.
THERE IS A JUNCTION BOXES LOCATED REAR OF THE BUILDING AN UNDER THE EAVE AREA WHICH
HAS BEEN MODIFIED. THIS ENCLOSURE HAS CUT OUTS WHICH NOW VIOLATES THE LISTING.

THERE ARE MULTIPLES ELECTRICAL DEVICES AND ENCLOSURES WHICH ARE NOT PROTECTED. THEY HAVE MISSING COVER PLATES, NOT PROPERLY SUPPORTED. AND NOT WEATHER TIGHT.
THERE IS NON METALLIC SHEATHED CABLE BEING USED OUTDOORS UNDER THE EAVE AREA AND UNDER THE CARPORT. THERE IS ALSO NON SHEATHED METALLIC CABLE BEING USED AS BRANCH CIRCUIT TO AN UNKNOWN LOCATIONS
THERE IS A FLOOD LIGHT ASSEMBLY ATTACHED TO THE FRONT STEEL CARPORT, THIS LUMINAIRE IS POWER AND CONNECT BY AN EXTENSION CORD WHICH RUNS INTO A SHED, THESE ARE UNAPPROVED WIRING METHODS. THIS OUTDOOR LIGHTING DOES NOT MEET THE REQUIREMENTS OF THE 2012 OUTDOOR LIGHTING CODE.
THERE IS A LIGHT ASSEMBLY ATTACHED TO THE FRONT OF THE BUILDING WHICH IS BEING POWERED BY A SERIES OF EXTENSION CORDS, THESE ARE UNAPPROVED WIRING METHOD. THE CONNECTION IS TO AN OUTLET WITH A RECEPTACLE WHICH IS NOT PROTECTED. THIS OUTDOOR LIGHTING DOES NOT MEET THE REQUIREMENTS OF THE 2012 OUTDOOR LIGHTING CODE.
THE GROUNDING ELECTRODE CONDUCTOR HAS BEEN CUT AT THE SERVICES LOCATION.

THE CURRENT POOL BARRIER IS A CHAIN LINK FENCE, THIS BARRIER IS NOT CODE COMPLIANT. THE LAST APPROVED BARRIER WAS AN IRON FENCE. THE CHANGE WAS DONE WITHOUT APPROVALS AND PERMITS.
THE REAR WOOD FRAME CARPORT'S ROOF DECKING AND COVERING HAVE EXTENSIVE AMOUNT OF DAMAGED. THE ROOF DECKING HAS MULTIPLE LARGE PENETRATIONS AND DETERIORATED WOOD MEMBERS. AN ESTIMATED AREA OF DAMAGE TO THE ROOF DECKING IS OVER 50 FEET BY 6 FEET WIDE.