Case: T19DV01717

Parcel: 129052050


Addresses:

2237 E 18TH ST

Inspection Status: Approved

Inspection History: INSP - INITIAL CODE ENFORCMENT

Date Description Inspector Results Comments
07/17/2019 INSP - INITIAL CODE ENFORCMENT Approved TUCSON POWER ELECTRIC CO, FILED A COMPLAINT ON THE CLEARANCE LACKING FOR THERE METER. THE METER IS LOCATED UNDER THE METAL PATIO WITH ZERO CLEARANCE. TEP DOES REQUIRE A 3 FOOT RADIUS CLEARANCE AROUND THE METER, TEP WOULD BE OK WITH A 1 FOOT RADIUS AROUND THE METER.
THERE IS NO DEAD FRONT TO THE MAIN DISCONNECT, ALSO THERE ARE MULTIPLE NON SHEATHED METALLIC CABLES WHICH RUN FROM THE MAIN DISCONNECT UNPROTECTED TO THE INTERIOR OF THE DWELLING.