Inspection History Details
Inspection Status: Approved
Inspection History: INSP - INITIAL CODE ENFORCMENT
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/17/2019 | INSP - INITIAL CODE ENFORCMENT | Approved | TUCSON POWER ELECTRIC CO, FILED A COMPLAINT ON THE CLEARANCE LACKING FOR THERE METER. THE METER IS LOCATED UNDER THE METAL PATIO WITH ZERO CLEARANCE. TEP DOES REQUIRE A 3 FOOT RADIUS CLEARANCE AROUND THE METER, TEP WOULD BE OK WITH A 1 FOOT RADIUS AROUND THE METER. THERE IS NO DEAD FRONT TO THE MAIN DISCONNECT, ALSO THERE ARE MULTIPLE NON SHEATHED METALLIC CABLES WHICH RUN FROM THE MAIN DISCONNECT UNPROTECTED TO THE INTERIOR OF THE DWELLING. |