Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T19CM09345
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/06/2020 | PLUMBING - FINAL | Approved | ||
12/27/2019 | PLUMBING - FINAL | Denied | 1- The air pressure test gage was just above 2 psi. The pressure test shall be a minimum of 10 psi. Check the system for leaks. 2- Shall provide (3) sheet metal screws per joint on furnace flu vent and remove the mechanical tape around the vent connector to the double wall flu vent. 3- Shall remove the flex connector on the water heater t & p drain and terminate it 6 inches above the floor. |
|
12/20/2019 | PLUMBING - FINAL | Not ready for Inspection |