Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T19CM09345

Parcel: 138132140


Addresses:

242 W BILBY RD


Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T19CM09345

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
01/06/2020 PLUMBING - FINAL Approved
12/27/2019 PLUMBING - FINAL Denied 1- The air pressure test gage was just above 2 psi. The pressure test shall be a minimum of 10 psi. Check the system for leaks.
2- Shall provide (3) sheet metal screws per joint on furnace flu vent and remove the mechanical tape around the vent connector to the double wall flu vent.
3- Shall remove the flex connector on the water heater t & p drain and terminate it 6 inches above the floor.
12/20/2019 PLUMBING - FINAL Not ready for Inspection