Permit: T19CM09345

Parcel: 138132140


Addresses:

242 W BILBY RD


Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Permit Number - T19CM09345

Inspection Description - PLUMBING - GAS PRESSURE TEST

Inspection Status - Approved

Date Description Inspector Results Comments
01/06/2020 PLUMBING - GAS PRESSURE TEST Approved Clear gas meter
Verbal clearance called in at 11:13 am.
12/27/2019 PLUMBING - GAS PRESSURE TEST Denied 1- The air pressure test gage was just above 2 psi. The pressure test shall be a minimum of 10 psi. Check the system for leaks.
2- Shall provide (3) sheet metal screws per joint on furnace flu vent and remove the mechanical tape around the vent connector to the double wall flu vent.
3- Shall remove the flex connector on the water heater t & p drain and terminate it 6 inches above the floor.
12/26/2019 PLUMBING - GAS PRESSURE TEST Denied 1- No access to the inspection area at the time of inspection request
12/20/2019 PLUMBING - GAS PRESSURE TEST Not ready for Inspection No gauge installed